Simplex Contact Closure DACT Installation And Programming Instructions page 36

Digital alarm communication transmitter
Table of Contents

Advertisement

Programming the CCDACT,
Programming(Continued)
Comm.
Format
1
3/1 Standard 1800/2300 Hz
(See Note 1)
2
3/1 Standard 1900/1400 Hz
(See Note 1)
3
4/2 Standard 1800/2300 Hz
(See Note 1)
4
4/2 Standard 1900/1400 Hz
(See Note 1)
5
SIA
6
RADIONICS BFSK
1800/2300 Hz
7
RADIONICS BFSK
1900/1400 Hz
Continued
Table 3-1 shows UL-listed receivers that are compatible with the CCDACT.
Table 3-1. CCDACT / Receiver Compatibility
Osborne/
ADEMCO
Hoffman
Silent Knight
685
Quickalert
(See Notes
Model II
2, 6)
YES
YES
(See Note 3)
YES
YES
(See Note 3)
YES
YES
(See Note 3)
YES
YES
(See Note 3)
YES
NO
(See Note 4)
YES
YES
(See Note 3)
YES
YES
(See Note 3)
NOTES:
1. 10 and 20 PPS (Pulses Per Second).
2. With 685-8 Line Card.
3. With 9032 Line Card.
4. With 9004 Line Card.
5. With Rec-11 Line Card.
6. These receivers are also Factory Mutual approved.
Before testing the CCDACT to communicate with the central station, make sure
your laptop PC is unplugged from the DACT.
Do not direct-connect the CCDACT to a coin telephone or party line. The line
must be dedicated to the CCDACT and must not have any TELCO features such
as "Call Waiting", etc.
3-6
firealarmresources.com
RECEIVER
FBI
RADIONICS
CP220FB
9000
(See Notes
5, 6)
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
SUR-GARD
6500
MLR2-DG
(See Note 6)
YES
YES
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading