Simplex Contact Closure DACT Installation And Programming Instructions page 39

Digital alarm communication transmitter
Table of Contents

Advertisement

Programming the CCDACT,
Programming (Continued)
Continued
17. Press [↵] or [↓]. Screen displays:
Scroll to the choice that identifies the phone lines(s) you want to use to
report this condition.
18. Press [↵] or [↓]. Screen displays:
Scroll to the choice that identifies the phone lines(s) you want to use to
report this condition.
19. Press [↵] or [↓]. Screen displays:
Scroll to the choice that identifies the phone line(s) you want to use to report
this condition.
20. Press [↵] or [↓]. Screen displays:
Scroll to choice that identifies the phone line(s) you want to use to report
this condition.
Note:
To test the CCDACT manually, position SW1 in its ON (up) position
for a minimum of 3 seconds. Then return it to the OFF position. After
a short delay, the green LED will flash to indicate a call attempt.
(Switch SW1 is found approximately 1.5 in. (3.71 cm) to the right of
P1.)
3-9
firealarmresources.com
17>ST AC FAIL
[P1 ELSE P2]
18>ST ACFAIL REST.
[P1 ELSE P2]
19>ST AUTO COMM TEST
[P1 ELSE P2]
20>ST MAN. COMM TEST
[P1 ELSE P2]
Continued on next page