Event Logbook; Event History - Endress+Hauser Liquiphant FTL51B Operating Instructions Manual

Vibronic hart point level switch for liquids
Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Diagnostics and troubleshooting
4)
If operating via FieldCare, the event list can be displayed with the "Event List/HistoROM" function in FieldCare.
44
Diagnostic
Short text
number
495
Diagnostic event
simulation active
538
Configuration Sensor Unit
invalid
Diagnostic of process
801
Supply voltage too low
802
Supply voltage too high
805
Loop current faulty
806
Loop diagnostics
807
No Baseline due to insuf.
volt. at 20 mA
825
Electronics temperature
826
Sensor temperature out of
range
842
Process limit
846
HART Non-Primary
Variable Out of Limit
847
HART Primary Variable
Out of Limit
848
HART Device Variable
Alert
900
Process alert frequency
too low
901
Process alert frequency
too high
1)
Diagnostic behavior can be changed.
11.7

Event logbook

11.7.1

Event history

The Event list submenu provides a chronological overview of the event messages that
4)
have occurred
.
Navigation: Diagnostics → Event logbook
A maximum of 100 event messages can be displayed in chronological order.
The event history includes entries for:
• Diagnostic events
• Information events
Remedy instructions
Deactivate simulation
1. Check sensor configuration
2. Check device configuration
Increase supply voltage
Decrease supply voltage
1. Check wiring
2. Replace electronics
1. Check supply voltage
2. Check wiring and terminals
Increase supply voltage
1. Check ambient temperature
2. Check process temperature
1. Check ambient temperature
2. Check process temperature
1. Check process density
2. Check fork
Check device specific diagnosis.
Check device specific diagnosis.
Check device specific diagnosis.
Check process conditions
Check process conditions
Liquiphant FTL51B HART
Status
Diagnostic
signal
behavior
[from the
[from the
factory]
factory]
S
Warning
M
Warning
F
Alarm
S
Warning
F
Alarm
1)
M
Warning
M
Warning
1)
S
Warning
1)
S
Warning
F
Alarm
S
Warning
S
Warning
S
Warning
1)
M
Warning
1)
M
Warning
Endress+Hauser

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hart liquiphant ftl51b

Table of Contents