Mounting
14
5.1.3

Avoid buildup

• Use short installation sockets to ensure that the tuning fork projects freely into the
vessel
• Leave sufficient distance between the buildup expected on the tank wall and the tuning
fork
 7
Installation examples for a highly viscous process medium
5.1.4

Take clearance into consideration

Allow sufficient space outside the tank for mounting, connection and settings involving
the electronic insert.
 8
Take clearance into consideration
5.1.5

Support the device

Support the device in the event of severe dynamic load. Maximum lateral loading capacity
of the pipe extensions and sensors: 75 Nm (55 lbf ft).
Liquiphant FTL51B HART
A0033239
A0033236
Endress+Hauser