Take Viscosity Into Consideration - Endress+Hauser Liquiphant FTL51B Operating Instructions Manual

Vibronic hart point level switch for liquids
Hide thumbs Also See for Liquiphant FTL51B:
Table of Contents

Advertisement

Liquiphant FTL51B HART
Endress+Hauser
A
D
 4
Typical switch points. Unit of measurement mm (in)
A
Installation from above
B
Installation from below
C
Installation from the side
D
Switch point
5.1.2

Take viscosity into consideration

Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
 5
Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
Make sure that the liquid can run off the tuning fork easily.
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
The tuning fork must be located outside the installation socket!
 6
Installation example for a highly viscous liquid. Unit of measurement mm (in)
B
D
> 25 (0.98)
> 40 (1.57)
Mounting
C
D
A0037915
A0033297
A0037348
13