Liquiphant FTL51B HART
Endress+Hauser
A
D
4
Typical switch points. Unit of measurement mm (in)
A
Installation from above
B
Installation from below
C
Installation from the side
D
Switch point
5.1.2
Take viscosity into consideration
Low viscosity
Low viscosity, e.g. water: < 2 000 mPa⋅s
It is permitted to position the tuning fork within the installation socket.
5
Installation example for low-viscosity liquids. Unit of measurement mm (in)
High viscosity
NOTICE
Highly viscous liquids may cause switching delays.
‣
Make sure that the liquid can run off the tuning fork easily.
‣
Deburr the socket surface.
High viscosity, e.g. viscous oils: ≤ 10 000 mPa⋅s
The tuning fork must be located outside the installation socket!
6
Installation example for a highly viscous liquid. Unit of measurement mm (in)
B
D
> 25 (0.98)
> 40 (1.57)
Mounting
C
D
A0037915
A0033297
A0037348
13