Liquiphant FTL64
Elements on the electronic
insert
Terminals
Local operation
Endress+Hauser
46
Example of electronic insert FEL64DC
1
COM interface for additional modules (LED module, Bluetooth module)
2
LED, red, for warning or alarm
3
LED, yellow, switch status
4
LED, green, operational status (device is on)
5
Test button, activates functional test
6
Terminals (3 to 8), relay contact
7
DIP switch for configuring density, 0.7 or 0.5
8
DIP switch for configuring MAX/MIN safety mode
9
Terminals (1 to 2), power supply
Terminals for cable cross-section up to 2.5 mm
Operation at electronic insert
MAX/MIN fail-safe mode
A
MAX
47
Switch position on the electronic insert for fail-safe mode MAX/MIN
A
MAX (maximum fail-safe mode)
B
MIN (minimum fail-safe mode)
• Minimum/maximum quiescent current safety can be switched at the electronic insert
• MAX = Maximum safety: When the tuning fork is covered, the output switches in the direction of
demand. Use this for overfill prevention, for example.
• MIN = Minimum safety: When the tuning fork is uncovered, the output switches in the direction of
demand. Use this for dry-running protection of pumps, for example.
Density switchover
48
Switch position on the electronic insert for density
Factory setting for density: 0.7
1
2
3 4
5
COM
MAX
>0,7
3 5
MIN
>0,5
U = 9...20 V DC
L+
L-
4
3 4 5
6
1
2
9
8
7
2
(14 AWG). Use ferrules for the wires.
B
ρ > 0.7
6
8
7
7 8
6
MIN
ρ > 0.5
A0037705
A0033470
A0033471
37