Modules
7.2.12 Zone Accessory Options
1.
Do steps 1 through 5 of Section 7.2.9.
2.
Press 3 to edit the Zone's Accessory options.
Single or Multi-Station Cadence Pattern (choose from Patterns 00 to 02, 23 if you are using Velociti.
3.
Choose from 00-16, 23 is using SD devices). See Appendix C.
CO Single and Multi-station Cadence (choose from Cadence Patterns 00 to 02, 23 for Velociti devices).
4.
To select the Local Zone, select Y or N, for Yes or No).
NOTE: The B200S Sounder base provides the recommended CO cadence pattern.
7.2.13 View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the Installer Code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 2 to enter Zone Menu.
4.
Press 2 to view Zone Points.
5.
Enter the number of the zone you want to view, then press <Enter>.
7.2.14 Group
An Output Group is made up of output points that were programmed to respond in the same way. Output Groups simplify programming,
because you do not have to program each individual point. After you define the characteristics of Output Groups, you can assign each
point to the appropriate group. Up to 125 output groups can be defined.
7.2.15 Edit Group
In the Edit Group option, you can program the name of an Output Group (7.2.16, "Edit Group Name") and change the properties
(Section 7) of that group.
To edit a group, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Press 3 to enter Group Menu.
4.
Press 1 to Edit Group.
5.
Enter the number of the group you want to edit, then press <Enter>.
7.2.16 Edit Group Name
1.
To edit the Group Name, press 1.
You can use text to add a label to display a descriptive name for a group.
7.2.17 Edit Group Properties
1.
To edit the Group Properties, Press 2 from the Edit Group Menu.
The Edit Group Menu allows you to select options for each group for the following items:
Template Override: Y or N
When the Template Override is Yes, the Template Override Cadence is available. See Section 9.4.3 for more information.
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Figure 7.3 View Zone Points Screen
Group
OO1
Voice Group: Y
Select Switch:00
Allow Sys Overvide: N
Template Override: Y
Template Override
Cadence: 23
Figure 7.4 Group Properties Screen Programming Options
Zone Number
Properties
More
Programming