Basic Operation; 1: View Event History; 2: To Clear The Event History; 3: Conduct A Fire Drill - Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

System Operation

8.4 Basic Operation

Table 8.3 lists the steps required to set the system for Basic Operation.
Operation
Setting 19-0543 Time and Date
Disable / Enable a Point
Disable / Enable NACs by Template
Disable / Enable NACs by Group
Disable / Enable Zone Points
Disable / Enable Point
Inhibit Output Group
8.4.1 View Event History
Use the View Event History feature to display events on LCD. From the Main Menu, press 3 to select Event History. Events display with
the most recent Events appearing first. The panel can store up to 1000 Events. When it reaches its 1000-Event capacity, it will delete the
oldest Events to make room for the new Events as they occur. When you view the Event History in the panel, the most recent 500 Events
from every panel in the site display. When you use the HFSS Honeywell Fire Software Suite, the System will upload all 1000 Events
from every panel in the network.
8.4.2 To Clear the Event History
From the Installer Menu select 1 for System Tests. From the Test Menu, select 6 Clear History Buffer.
8.4.3 Conduct a Fire Drill
1.
From the Main Menu, press 1 for System Tests.
2.
Press 1 for Fire Drill. You will be prompted to press <Enter>.
3.
The drill will begin immediately after you press <Enter>.
4.
Press any key to end the drill. (If you do not manually press any key to end the fire drill, the fire drill will automatically time- out
after ten minutes).
If you installed a Fire Drill switch, you can activate the switch to begin the drill. You can deactivate the switch to end the drill.
5.
From the Main Menu, select 1 for System Tests. From the Test Menu, select 6 to Clear History Buffer.
8.4.4 Conduct an Indicator Test
The Indicator Test checks the annunciator LEDs, PZT, and LCD display.
1.
From the Main Menu, press 1 for System Tests.
2.
Press 2 for Indicator Test. The System turns on each LED several times, beeping the PZT as it does so. At the same time, it scrolls
each available character across the LCD. A problem is indicated if any of the following occurs:
• An LED does not turn on.
• You do not hear a beep.
• All four lines of the LCD are not full.
This test takes approximately 15 seconds to complete. You can manually press any key to end the test, while the test is still in progress.
When the test ends, you will be returned to the <Test Menu>.
8.4.5 Conduct a Walk Test
From the Main Menu, press 1 for System Tests.
WARNING: If you use any Alarm Verification Zones, the User will be asked if they want to disable Alarm Verification during
Walk Test. This occurs for either Walk Test option.
3.
Select 3 for Walk Test-No Rpt. The LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER = start test" on Line 3. If
you select this option, Central Station Reporting will be disabled while the test is in progress.
4.
Select 4 for Walk Test-with Rpt. The LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER = start test" on Line 3.
If you select this option, central station reporting will occur as normal during the walk test.
The panel generates a TEST report to the Central Station when the Walk Test begins. During a Walk Test, the panel's normal fire
alarm function is completely disabled, placing the panel in a local trouble condition. All zones respond as 1-Count Zones (for
example, it responds when a single detector is in alarm) during a Walk Test. Each alarm initiated during the Walk Test will be
reported and stored in the Event History Buffer.
62
1.
To set the Date and Time, select Option 4.
2.
Make changes in the fields on the screen.
3.
To move the cursor to each field, press the <Right> arrow.
4.
To select options in the fields, press the <Up> or <Down> arrow keys.
After you set the date and time, press <Enter>.
1.
Select 2 for Point Functions.
2.
Select 1 for Disable/Enable Point.
1.
Press 1 for Disable NACs by Template, press 2 to Enable NACs by Template. Use the
<Up> or <Down> arrow keys to move through the list of templates. Press <Enter> to
select the current template.
1.
Press 3 to Disable NACs by Group, or press 4 to Enable NACs by Group.
2.
Use the <Up> or <Down> arrow keys to move through the list of groups.
3.
Press <Enter> to select the group highlighted.
1.
Press 5 to Disable Zone Points, or press 6 to Enable Zone Points.
2.
Use the <Up> or <Down> arrow keys to move through the list of zones. Press <Enter>
to select the zone highlighted.
1.
Press 7 to Disable /Enable Point.
2.
Choose Module.
3.
Use the <Up> or <Down> arrow keys to choose Point and press <Enter>.
4.
Press <Right> arrow to disable or enable point.
Inhibiting an Output Group prevents the group from being used by System Mapping. While the
Group is inhibited, no event in the system can activate the Output Group.
1.
Press 8 to Inhibit Output Group (OPG).
2.
Use the <Up> or <Down> arrow keys to select the Group to be inhibited.
3.
Press <Right> arrow to inhibit the Group.
4.
Press <Right> arrow again to enable the Group.
Table 8.3 Basic Operation Steps
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Steps to Set the Basic Operations
Basic Operation

Advertisement

Table of Contents
loading

Table of Contents