To manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All
options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
Before you complete any customized programming, you must first run JumpStart
oughly test the system. The reason you test the system after JumpStart Auto-programming is to activate JumpStart Auto-programming
to automatically program the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to con-
firm the integrity of the installation prior to performing any custom programming. After you determine the hardware is properly
installed, you can perform custom programming.

7.1 UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES: This product
incorporates field programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all
as indicated below.
Programming Option
Time Options
Time Options
Display Oldest Event
Alarm Verification

7.2 Modules

This section lists the options available under the Module Option in the Program Menu. The types of modules available for the control
panel are as follows:
• RA-1000 LCD Annunciator • 5824 Serial/Parallel input/output • 5880 LED Input/Output module • GFPS-6S NAC Expander
7.2.1 Edit Modules
If you select Edit Modules, you can edit the module name and class of wiring (Class A or Class B) features. To edit an existing module,
follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Press 1 to enter Module menu.
4.
Press 1 to edit a module.
5.
Use the <Up> or <Down> arrows to select the module you want to edit.
7.2.2 Editing Module ID
1.
Press the <Up> or <Down> arrows key to modify the Module ID.
NOTE: You cannot edit the Module ID on Internal devices.
7.2.3 Naming Modules
You can assign an English name to a hardware module to make it easier to recognize on a display.
1.
To edit a Module Name, press the <Up> or <Down> arrows to select each character for the module's name (or press the <Right>
arrow to bypass the name edit). Press the <Right> arrow to move the cursor to the next character.
NOTE: To edit names, refer Appendix Appendix A:.
48

Section 7: Programming

Menu Item
Auto-Resound
Low AC Report Delay
Y (Enabled)
N (Disabled)
Alarm Verification
Table 7.1 Programming Criteria
Figure 7.1 Edit Module Name Programming Screen Example
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
IMPORTANT!
®
Permitted in UL
Possible Settings
864 (Y/N)
Yes
4 or 24 hrs
Yes
0–30 hours
Yes
Yes & No
No
Yes & No
Yes
60-250 (confirmation period)
Auto-programming. After JumpStart is run, thor-
Settings Permitted in UL 864
4 hours if using SWIFT devices
1–3
Yes
No
60