Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual page 57

Addressable fire alarm control panel
Table of Contents

Advertisement

System Options
AlarmNet Timers
1.
Enter the Installer Code. The control panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 4 for AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows
• Ethernet: *5 minutes, 3 minutes, 90 seconds, 75 seconds, none, 30 days, 24 hours, 1 hour.
• Cellular: *24 hours, none, 30 days
• Old Alarm: *30 minutes, 15 minutes, 10 minutes, none, 24 hours12 hours, 6 hours, 4 hours,2 hours, 1 hour*defaults
• AlarmNet Timers
Phone Line Gains
1.
Enter the Installer Code. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 5 for Phone Line Gains
6.
The available options:
• Dialing: Low, *High (default), Normal
• Reporting: *Low (default), High, Normal
Daytime/Nighttime Sensitivity
If you need to change the time that sensitivity levels take effect (that is, the time that "Day" and "Night" begin), follow these steps.
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
From the System Options Menu, select 2 for Day/Night Sense.
A screen similar to the one shown in Figure 7.11 will display
.
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Figure 7.9 AlarmNet Timers
Figure 7.10 Phone Line Gains
Figure 7.11 Changing Day/Night Sensitivity Time
Programming
57