Section 9: Reporting; Receivers Compatible With The Control Panel - Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for
SIA and Contact ID formats.

9.1 Receivers Compatible with the Control Panel

Table 9.1 shows receivers compatible with the control panel.
Silent Knight by
Honeywell
Honeywell Security
Ademco
Ademco
Sur-Gard
Osborne Hoffman
Event Description
System Events
AC power low trouble
AC power low trouble restore
Auto dialer test communications
trouble line 1
Auto dialer test communications
trouble line 1 restore
Auto dialer test communications
trouble line 2
Auto dialer test communications
trouble line 2 restore
Automatic test normal
Automatic test off normal
Battery voltage trouble
Battery voltage trouble restore
Date changed event
ECS Reset
Emergency System Overridden
Emergency System Overridden
Restore
Fire drill has begun
Fire drill has ended
F1 Mapping Inhibited
F1 Mapping Inhibited Restoral
F2 Mapping Inhibited
F2 Mapping Inhibited Restoral
F3 Mapping Inhibited
F3 Mapping Inhibited Restoral
F4 Mapping Inhibited
F4 Mapping Inhibited Restoral
Fire Reset
Fire System Overridden
Fire System Override Restore
Ground fault condition trouble
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019

Section 9: Reporting

Manufacturer
Model 9800
Model 9000 (SIA formats)
AlarmNet 7810-ir
MX8000
Model 685 (Contact ID )
SG-MLR2-DG (V. 1.64 or higher)
Quickalert
Table 9.1 : Receivers Compatible with the Control Panel
SIA pi Modifier
Module ID
SIA
# (If Any)
Event
Codes
System Events are reported when either "Report by Point" or Report by Zone is selected
AT
AR
YC
YK
YC
YK
RP
RY
YT
YR
JD
OR
QS
QR
FI
FK
FT
FJ
FT
FJ
FT
FJ
FT
FJ
OR
FS
FR
YP
Table 9.2 : Reporting Formats Table
Model
SIA Reporting Format
SIA
Parameter Fixed Length
Format NN - panel
ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
0
ATNN000000
0
ARNN000000
1
YCNN000001
1
YKNN000001
2
YCNN000002
2
YKNN000002
0
RPNN000000
0
RYNN000000
Exp. ID
YTNNXX0000
Exp. ID
YRNNXX0000
0
JDNN000000
1
ORNN000001
0
QSNN000000
0
QRNN000000
0
FINN000000
0
FKNN000000
2001
FTNN002001
2001
FJNN002001
2002
FTNN002002
2002
FJNN002002
2003
FTNN002003
2003
FJNN002003
2004
FTNN002004
2004
FJNN002004
0
ORNN000000
0
FSNN000000
0
FRNN000000
Exp. ID
YPNNXX0000
Format
SIA and Contact ID
SIA
IP and Cellular Receiver,
Contact ID only
SIA and Contact ID
Contact ID
SIA and Contact ID
SIA and Contact ID
Contact ID Reporting Format
Qualifier
Event
Group #
Code
1
301
00
3
301
00
1
350
Receiver # 001
3
350
Receiver # 001
1
350
Receiver # 002
3
350
Receiver # 002
1
602
00
1
608
00
1
302
Exp. ID
3
302
Exp. ID
1
625
00
1
401
00
1
244
00
3
244
00
1
604
00
3
604
00
1
570
00
3
570
00
1
570
00
3
570
00
1
570
00
3
570
00
1
570
00
3
570
00
1
401
00
1
245
00
3
245
00
1
310
Exp. ID
Contact #
000
000
000
000
000
000
000
001
000
000
000
000
001
001
002
002
003
003
004
004
000
000
000
000
71

Advertisement