Programming Overview

6.3 Mapping LED Points

Figure 6.6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output
groups for each zone, one for alarms and one for troubles. (LED points are available when Model 5880 is used with the system).
Zone 1
Manual Pull Alarm
Zone 1
Detector Alarm
Zone 1
Trouble
Zone 2
Manual Pull Alarm
Zone 2
Detector Alarm
Zone 2
Trouble
Figure 6.6 Example of LED Points Mapped to Output Groups (applies to Model 5880)

6.4 Programming Using the HFSS Software Suite

You can use the HFSS Honeywell Fire Software Suite to program the control panel onsite (personnel will need to be onsite during the
upload or download process). HFSS is a software package that lets you easily program the control panel using a Windows-based com-
puter. HFSS is needed for Mapping. When you use the HFSS Software Suite, you can set up the programming options for the control
panel, save the options in a file, then download the file to the control panel. You can connect to the control panel directly using the
onboard USB or Ethernet. To obtain updates, refer to the Gamewell-FCI ESD website at www.gamewell-fci-esd.com.

6.5 Programming Using an Annunciator

You can program the control panel from a system annunciator, using either the control panel's on-board annunciator or RA-1000 remote
annunciator.
The following subsections describe programming basics, including a description of editing keys available for programming and how to
move through programming menus. Section 7 contains specific information about individual programming options.
NOTE: Mapping cannot be programmed through the on-board and remote annunciators. Mapping is only available through
HFSS Honeywell Fire Software Suite, up/downloading software.
6.5.1 Entering / Exiting the Program Menu
To enter the Program Mode:
1.
Enter the Installer code if requested.
2.
Select 7 to access the Program Menu.The menus described in Section 7 of this manual will display. Section 6.6 of this manual is a
quick reference listing all programmable options and JumpStart Auto-programming defaults.
To Exit Program Mode:
When you complete working with the menus, press the <Left Arrow> button several times until you exit from the Programming Mode.
Two prompts will display. Use the first prompt to exit the Program Menu (select Yes or No as appropriate). Use the second prompt to
accept all changes. If you select No, any changes you made since you entered the Program Menu will have no effect.
42
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Output Group 1
Red LED 1
Alarm Outputs
(Horns, Strobes, etc.)
Output Group 2
Yellow LED 2
Maintenance Room Sounder
Output Group 3
Red LED 3
Alarm Outputs
(Horns, Strobes, etc.)
Output Group 4
Yellow LED 4
Mapping LED Points
An alarm in Zone 1 will
activate Red LED 1 and any
other required outputs.
A trouble in Zone 1 will
activate Yellow LED 2 plus
any other needed outputs.
(In this example, it activates
a sounder in a Maintenance
Room.
An alarm in Zone 2 will
activate Red LED 3 and any
other required outputs.
A trouble in Zone 2 will
activate Yellow LED 4.