Operation Mode Behavior Conditions
Operation
Mode
A smoke detector goes into
alarm or a pull station is
activated.
CO detector
goes into
alarm.
Alarm
If more than 3
categories are
active at a
single time
screen will
display as shown.
The system detects a
supervisory condition.
Supervisory
The system detects a
Supervisory
supervisory condition with a CO
detector
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Operation Mode
Condition
The communicator seizes control of the phone
line and calls the central station.
The on-board annunciator sounds a loud,
steady beep (any notification devices attached
to the system will also sound).
GENERAL ALARM LED flashes.
The LCD displays a screen similar to this one.
The communicator seizes control of the phone
line and calls the central station.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second on,
one second off.
SUPERVISORY LED flashes.
The LCD displays a screen similar to this one.
Table 8.4 : Operation Mode Behavior (Continued)
System Behavior
System Operation
Operation Mode Troubleshooting
Options
Press the down arrow to view the alarm. A
screen similar to this one displays.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator (and
any notification devices attached to the system).
When the alarm condition clears, press RESET
and enter a code (or activate the key) to restore
the panel to normal.
Press down arrow to view the supervisory
condition. A screen similar to this one displays.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator.
Once the supervisory condition has been
corrected, the system will restore itself
automatically.