2: Point Programming For An Internal Or An External Power Module; 3: Point Programming For 5880 Modules - Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
7.3.2 Point Programming for an Internal or an External Power Module
To program for an internal or external Power Module Points, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for the Program Menu.
3.
Press 4 to enter the Point Menu.
4.
Press the <Up> or <Down> arrows to select the desired module. Press <Enter>. Refer to Section 6.5 for available choices.
5.
<Enter> the number of the circuit or point you want to edit. Refer to Table 7.5 for available selections. Press <Enter>.
6.
To select the type, press the <Up> or <Down> arrows, then press <Enter>.
7.
To select the function, press the <Up> or <Down> arrows, then press <Enter>.
8.
To select the group, press the <Up> or <Down> arrows, then press <Enter>.
9.
Edit point name. Press the <Right> arrow to bypass the Point Name Edit. See Section 7.3.
10. Repeat Steps 1 through 10 for all circuits.
Choices
Enter Point or Circuit
Select Type
Select Type
Select Group
Edit Name
*Only applicable on
54
Function Selections
Type Selections
UNUSED
NOTIF OUT
CTRL CKT
AUX PWR
CONSTANT
RESETTABLE
DOOR
AUX SYNC
B SWITCH*
MAN PULL
WATERFLOW
SUPERVSY
TAMPER
FIRE DRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
STATUS POINT
A SWITCH*
Same as B SWITCH
B DETECTOR*
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
A DETECTOR*
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
Table 7.5 Menu choices for Internal/External Power Modules
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
for each Type
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Sounder Sync auxiliary power for System Sensor
Refer to comments column of
Table 7.4 for description of these options
Latch or Non-latching feature only appears for
waterflow, supervisory, tamper, zone aux1,
zone aux2, system aux1, and system aux2
Non-latching - Used to activate an ancillary
Output Group that does not active alarm, sound
PZT, display status or report events. Reset has
no affect on this point
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire CO
Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-wire CO
Supervisory detectors
Group or Zone selection will appear depending on the type
selected
Edit name. See Section 7.3.2
Comments
Point

Advertisement

Table of Contents
loading

Table of Contents