Wiring Specifications - Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Installation Instructions Criteria

3.4 Wiring Specifications

Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone communication or cause false alarms.
To avoid induced noise, follow these guidelines:
Isolate input wiring from high current output and power wiring. Do not pull the one multi-conductor cable for the entire panel.
Instead, separate the wiring as follows:
Do not pull wires from the different groups through the same conduit. If you must run the wires together, do so for as short a
distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You must route high and low voltages
separately.
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it could induce noise into the
sensitive microelectronics or pick up unwanted RF noise from the high speed circuits. See Figure 3.1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire
through ferrite shield beads or by wrapping it around a ferrite toroid.
14
High voltage
SLC loops
Audio input/output
Notification circuits
SBUS
Relay circuits
Battery
Figure 3.1 Wire Routing Example
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
AC power Terminals
Phone line circuits
NAC1 through NAC2
Table 3.2 Wiring Terms
Battery
Wiring Specifications
NAC / Aux Power
Outputs
SBUS
Devices
SLC IN/OUT

Advertisement

Table of Contents
loading

Table of Contents