System Options
AC Report Delay
NOTE 1: You must select 1-3 hours in UL Central Station installations and UL Remote Signaling installations.
You can adjust the number of hours before a Low AC Report will be sent to the Central Station. To program Low AC Report Delay,
follow these steps:
NOTE 2: Steps continued from step 7 of subsection, Alarm Verify.
3.
Enter the number of hours before a Low AC report will be sent to the Central Station, then press <Enter>.
AC Line Frequency
The panel's AC Line Frequency is selectable for 60 Hz or Internal. AC Frequency feature dictates how the control panel will calculate
the time based on the AC Line Frequency used in the installation site. You can use the "Internal" option in areas where the AC Line Fre-
quency is not dependable and you want the control panel to calculate the time from the internal crystal. The internal crystal is not as
accurate as the AC power source and 60 Hz should normally be selected. The panel defaults to the 60 Hz. selection.
To change the AC Line Frequency, continue programming from step 9 above:
1.
Select 60 or Intl, by pressing the <Up> or <Down> arrow keys then press <Enter>.
Clock Display Format (AM/PM or Military)
To change the System Clock Display format, continue programming from step 8 above:
1.
Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the <Up> or <Down> arrow
keys, then press <Enter>.
Auto-Resound (4 or 24 hours)
You can modify the System Resound Time period from the default value, 24 hours to 4 hours. This setting adjusts when the FACP will
automatically resound events after being silenced. Set this option to 4 hours when you use SWIFT devices.
7.4.5 Miscellaneous Options
Through this Programming option you can turn on or off the Strobe Synchronization during silence, display status at idle (auto display
event), report by zone or point, and single key acknowledge. To edit miscellaneous options, do the following:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Miscellaneous Options.
Strobes Active when Silenced
When "SYNC Strobe:" is selected as Y (Yes), the strobes will continue to flash when the system is silenced and will stop flashing when
the system is reset.
NOTE: The "SYNC Strobe:" only functions with outputs that use a synchronized output pattern.
5.
Press the <Up> or <Down> arrow keys to toggle this selection between Y (Yes) or N (No).
6.
Press <Right> arrow key or <Enter> to make your selection and move to the next programming option.
Auto Display Events
When this feature is programmed Y (Yes), the highest priority event of the system in control will automatically display on the control
panel and remote annunciators after there has been no activity on any system touch pad for two minutes.
1.
Press the <Up> or <Down> arrow keys to toggle this selection between Y (Yes) or N (No).
2.
Press <Right> arrow key or <Enter> to make your selection and move to the next programming option.
7.4.6 Daylight Saving Options
To edit Daylight Savings, do the following:
NOTE: For UL installations, the Alarm Verification Time cannot be less than 60 seconds.
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 6 for Daylight Savings.
Automatic Daylight Saving Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If you do not enable (set to No) this feature, the
Daylight Saving Time change is not made to the system clock.
1.
To enable or disable DST adjustment, continue programming:
2.
To select Y (enabled) or N (disabled), press the <Up> or <Down> arrow, then press <Enter>.
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Water Flow Delay: 01s
Alarm Verify: 060s
AC Report Delay: 03h
<Low AC (-030h)> More
Figure 7.14 Low AC Report Delay Programming Screen
Low AC Report
delay
Programming
59