Alter Status
Soft Keys
ALARM HISTORY: Press to clear Alarm history.
EVENT HISTORY: Press to clear Event history.
ALL HISTORY: Press to clear both Alarm and Event history.

4.6 Walk Test

Walk Test allows the user to test the entire fire alarm system while away from the control panel.
There are two types of Walk Test - Basic and Advanced - and each type operates in audible mode.
Walk Test results are sent to the printer and to Event History as "Test".
WARNING:
!
Physically disconnect all releasing devices before starting Walk Test. It is not sufficient to disable in
any other manner.
WARNING:
!
Walk Test mode can deactivate fire protection. Observe the following important precautions.
IMPORTANT!
• Prior to Walk Test, secure all protected buildings, and notify the building owner/operator,
fire department, and other pertinent personnel that testing is in progress.
• Immediately after Walk Test is completed, notify the same people that testing is complete
and the system is restored to normal operation. Reconnect releasing devices.
• Walk Test will "time out" and return to normal operation after one hour when no Walk Test
activations have occurred during that time.
• Walk Test may be exited at any time by pressing the ABORT soft key on the screen
NOTE: Walk Test will not start if any devices are active (i.e., fire alarms, security, supervisories
or pre-alarms.) To perform a walk test while a device is active, disable the device and press the
System Reset button.
68
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 3 , 2 0 0 5
C L E A R H I S T O R Y
A L A R M H I S T O R Y
E V E N T H I S T O R Y
A L L H I S T O R Y
Figure 4.8 Clear History Screen
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005