Programming
Daylight Saving Time Start and End
Use the Daylight Saving Time Start and End option to adjust the week and month Daylight Saving Time (DST) starts and ends. For this
feature to work, you must enable (set to Yes) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The
default values for the DST Start and End are as follows:
DST Start:
The second Sunday in March
DST End:
The first Sunday in November
To set the start and end for Daylight Saving Time, do the following.
1.
To select the Week (1st, 2nd, etc.) Daylight Saving Time starts, press the <Up> or <Down> arrows.
Then, press <Enter> to make your selection and move the cursor to the Month setting.
2.
To select the Month (January – December) Daylight Saving Time starts, press the <Up> or <Down> arrow.
Then, press <Enter> to make your selection and move to the DST End option.
3.
To select the Week (1st, 2nd, etc.) Daylight Saving Time ends, press the <Up> or <Down> arrow.
Then press <Enter> to make your selection and move to the Month setting.
4.
To select the Month (January – December) Daylight Saving Time ends, press the <Up> or <Down> arrow.
5.
Then, press <Enter> two times to make your selection and exit.
Edit Banner
When the system is in Normal condition, the banner displays a message on the panel LCD. If there are no alarms, no trouble conditions
exist, and no one is currently using the System Menus, the banner displays. You can create a customized message, which can be up to 40
characters, two lines of 20 characters each. If you do not create a customized message, the system uses the internal banner. You cannot
change the internal banner.
To customize the banner display message, do the following:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 7 for Edit Banner.
NOTE: To review instructions on editing the Banner, refer to Appendix B.
5.
To select each character of a word, press the <Up> or <Down> arrows, then press the <Right> arrow key to move to the next
character.
6.
When you complete the text, press <Enter> to move to line two of the custom banner.
7.4.7 SLC Family
The GWF-7075 supports Velociti SLC devices. You must configure the GWF-7075 to accept the protocol of the devices you want to
install. You cannot mix SLC devices of different protocols.
®
7.4.8 JumpStart
AutoProgramming
Panels support an incremental JumpStart.
JumpStart again, the additional devices are added, but you do not lose any of your previous custom programming
To run JumpStart Auto-programming:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 6 for the JumpStart Auto-programming.
4.
Press the <Up> or <Down> arrows to select "Yes" from the warning screen.
5.
Press <Enter>.
7.4.9 Restore Defaults
This option allows you to restore the panel back to factory defaults. All programming will be lost.
1.
Enter the Installer Code. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming.
3.
Select 7 for Restore Defaults.
4.
Press the <Up> or <Down> arrow keys to select <Yes> or <No> from the warning screen. Then press <Enter>.
60
®
For Example: After initial JumpStart and customization, if you add more devices, when you
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019