Module Information Monitor Data - Mitsubishi Electric MELSECQ Series User Manual

Hide thumbs Also See for MELSECQ Series:
Table of Contents

Advertisement

4 DATA USED FOR POSITIONING CONTROL

4.6.2 Module information monitor data

Item
Md. 10 Error
status
Md. 11 Warning
status
4 - 29
Downloaded from
ManualsNet.com
Storage details
At error occurrence, the bit corresponding to the
error occurrence axis turns ON.
0: Normal (OFF)
1: Error (ON)
(The error occurrence axis cannot be run)
When " Cd. 1 Axis error reset" (axis control data)
of the corresponding axis is turned ON, the error
status of the corresponding axis is cleared (to
zero). (Refer to "Chapter 13" for details.)
b15
b12
b8
b4
b0
Storage item
Not used
Axis 1 error
Axis 2 error
Axis 3 error
Axis 4 error
Axis 5 error
Axis 6 error
Axis 7 error
Axis 8 error
(For the QD70P4, b4 to b7 are "0" fixed.)
At warning occurrence, the bit corresponding to the
warning occurrence axis turns ON.
0: Normal (OFF)
1: Warning (ON)
When " Cd. 1 Axis error reset" (axis control data)
of the corresponding axis is turned ON, the
warning status of the corresponding axis is cleared
(to zero). (Refer to "Chapter 13" for details.)
b15
b12
b8
b4
b0
Storage item
Not used
Axis 1 warning
Axis 2 warning
Axis 3 warning
Axis 4 warning
Axis 5 warning
Axis 6 warning
Axis 7 warning
Axis 8 warning
(For the QD70P4, b4 to b7 are "0" fixed.)
search engine
Default value
0000
H
Meaning
0 : OFF
1 : ON
Meaning
0000
H
0 : OFF
1 : ON
MELSEC-Q
Storage buffer memory address
(Common for axis 1 to axis 8)
1600
1601
4 - 29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd70p4Qd70p8