Mitsubishi Electric MELSECQ Series User Manual page 210

Hide thumbs Also See for MELSECQ Series:
Table of Contents

Advertisement

13 TROUBLESHOOTING
Error
code
Setting range outside OPR
910
method
Setting range outside OPR
911
direction
Setting range outside OP
912
address
Setting range outside OPR
913
speed
Setting range outside creep
914
speed
Setting range outside
915
ACC/DEC time at OPR
Setting range outside
916
DEC/STOP time at OPR
Setting range outside
setting for the movement
917
amount after near-point dog
ON
Setting range outside stop
918
mode during path control
13 - 9
Downloaded from
ManualsNet.com
Error name
The setting value of " OPR. 1 OPR method" is outside
the setting range.
The setting value of " OPR. 2 OPR direction" is
outside the setting range.
The setting value of " OPR. 3 OP address" is outside
the setting range.
• The setting value of " OPR. 4 OPR speed" is outside
the setting range.
• The setting value of " OPR. 4 OPR speed" is lower
than " Pr. 6 Bias speed at start".
• The setting value of " OPR. 4 OPR speed" is higher
than " Pr. 5 Speed limit value".
• The setting value of " OPR. 5 Creep speed" is
outside the setting range.
• The setting value of " OPR. 5 Creep speed" is higher
than " OPR. 4 OPR speed".
• The setting value of " OPR. 5 Creep speed" is lower
than " Pr. 6 Bias speed at start".
The setting value of " OPR. 6 ACC/DEC time at OPR"
is outside the setting range.
The setting value of " OPR. 7 DEC/STOP time at
OPR" is outside the setting range.
The setting value of " OPR. 8 Setting for the
movement amount after near-point dog ON" is outside
the setting range.
The setting value of " Pr. 10 Stop mode during path
control" is outside the setting range.
search engine
Error
The module READY signal (X0) does not turn
ON.
MELSEC-Q
Operation status at error occurrence
13 - 9