Safety Function; Alarm Behavior And Alarm Current Output; Overall Safety Accuracy; Diagnostic Test Interval - ABB TTH200 Additional Instructions

Temperature transmitter; additional instructions for iec 61508 compliant devices
Hide thumbs Also See for TTH200:
Table of Contents

Advertisement

6
TTH200, TTR200, TTF200 TEMPERATURE TRANSMITTER | SM/TTX200/SIL-EN REV. E

5 Safety function

The TTH200-*H, TTR200-*H, and TTF200-*H transmitter are configurable single sensor channel (1 x RTD 2/3/4 wire, 1 x TC) digital
devices generating a temperature related analog 4 to 20 mA output signal. The safety function refers strictly to the analog output
signal.
The final device assembly consists of the device electronics TTH200-*H, TTR200-*H, or TTF200-*H, the attached temperature sensor,
the housing with optional connected LCD indicator and the related process connections.

Alarm behavior and alarm current output

When a critical error is detected, an alarm current according NAMUR NE 43 is generated which must be evaluated and processed by
the safety logic solver.
Detected failures by internal diagnostics generates the configured alarm current.
(See Appendix FMEDA Report: Fail detected by internal diagnostics)
There are two selectable modes for the alarm current:
HIGH ALARM (high alarm, maximum alarm current); this is the factory setting
LOW ALARM (low alarm, minimum alarm current)
The high alarm current can be configured in a range from 20.0 to 23.6 mA.
The factory setting is 22 mA.
The low alarm current can be configured in a range from 3.5 to 4.0 mA.
The factory setting is 3.6 mA.
In the following cases and by some electrical part failures, an error is forced independently of the configured alarm current to the low
alarm current range:
Detected runtime errors (e.g., by watchdog)
Detected memory errors (e.g., non-volatile data, RAM, ROM)
(See Appendix FMEDA Report: Fail low detected by safety logic solver)
Failures in some electrical parts are forcing independently of the configured alarm current the high alarm current range.
(See FMEDA Report: Fail high detected by safety logic solver)
The safety-related system (safety logic solver) must be able to detect both, the high and the low alarm state.
After switching on or restarting the transmitter electronics unit, the minimum alarm time is 10 to 15 seconds.

Overall safety accuracy

The value defined for the overall accuracy of the safety function for this device is ± 2 % of the measuring range.
The basic accuracy depends on the sensor model and is specified in the corresponding data sheets.

Diagnostic test interval

All safety-relevant errors are detected within a diagnostic test interval of 2 minutes.

Type classification

This device is declared as Type B complex element according IEC 61508.