Control Installation

Location
ENSURE that the wall controller is installed in a location that is within the range of
applicable WiFi access point. The distance is dependent on router model and brand.
Refer to your unit access point manual.
ENSURE that the wall controller is installed in a location that is within the
recommended range of RF signal of all connected zone devices. Maximum range is
30 metres line of sight and unobstructed.
Do not install the wall controller on external walls, directly below the supply air grille
or near other additional heat load sources, as these locations may alter
sensor readings.
Do not install the master controller near magnetic, metallic objects or install near
power cables as these may effect the wireless data signal it sends and receive.
Avoid looping excess cable.
Ensure there is ample space around the wall controller (100mm min) to ensure
proper air temperature reading and adequate access for service.
It is required to use the provided wall anchors and screws to secure device on
the wall.
DO NOT swap the master controller and secondary wall controller after setup.
Use the included 10m yellow Cat5E spec cables with RJ45 connectors & cable boot.
For longer cable requirements upto 30m in length, an optional 20m cable and RJ45
connector are available separately.
Use only the allocated indoor board terminal to connect the controllers.
4
approx. 1.5m
from the ground