Zone Control / Remote Sensor Installation
Location
ENSURE that the zone device (zone controller or remote sensor) distance
from wall controller (master or secondary) is within the recommended RF
range of 30m.
Do not install the zone devices on external walls, directly below the supply
air grille or near other additional heat load sources, as these locations may
alter sensor readings.
Do not install zone devices near magnetic, metallic objects or install near
power cables as these may effect the RF data signal it sends and receive
wall controller.
Avoid looping excess cable.
Ensure there is an ample space (100mm) around the zone device to ensure
proper air temperature reading and access for removal.
It is required to use the provided wall anchors and screws to secure the
device on the wall.
If a zone device is required to be replaced, remember to unpair the existing
controller and pair the new one to the master controller.
Use a maximum of 20m RJ45 cable.
Plug the power cable to its designated zone damper terminal or zone
module terminal (using 3-way cable joiner).
DO NOT use battery and zone power cable at the same time.
Dining
24.0 C
o
Zone OFF
AC OFF
OFF
Dining
24.0 C
o
Zone OFF
Dining
AC OFF
24.0 C
o
OFF
Zone OFF
AC OFF
OFF
Dining
24.0 C
o
Zone OFF
AC OFF
OFF
approx. 1.5m
from the ground
7