1MRS757656 A
2.3.6
2.3.6.1
Table 68:

DR.RDRE1 Disturbance recorder

IEC 61850 name
DR.RDRE1
.RcdMade.stVal
2.3.6.2
Table 69:

LD0.CCRDIF1 Current circuit failure protection

IEC 61850 name
LD0.CCRDIF1
.Alm.stVal
.Op.general
2.3.6.3
Table 70:

LD0.SEQRFUF1 Fuse failure protection

IEC 61850 name
LD0.SEQRFUF1
.Str.general
.Str3Ph.general
2.3.6.4
Table 71:

LD0.SECRSYN1 Synchrocheck

IEC 61850 name
LD0.SECRSYN1
.SynPrg.stVal
.FailCmd.stVal
.FailSyn.stVal
REM620
Point List Manual

Protection related functions

DR.RDRE1 Disturbance recorder
SA name
LD0.CCRDIF1 Current circuit failure protection
SA name
FAIL
ALARM
LD0.SEQRFUF1 Fuse failure protection
SA name
FUSEF_U
FUSEF_3PH
LD0.SECRSYN1 Synchrocheck
SA name
SYNC_INPRO
CMD_FAIL_AL
CL_FAIL_AL
Description
DR recording made
Description
Fail Alarm
Fail Operate
Description
General start
Three-phase start
Description
Synch in progress
CB close request failed
CB close command failed
Section 2
DNP3 data mappings
Values
1=Made
Values
1=Alarm
1=Operate
Values
1=Start
1=Start
Values
1=In progress
1=Failed
1=Failed