Power Requirements; Spsu-S Units - Power Usage/Requirements; Table 10: Rack Clearance Requirements - Mellanox Technologies Vantage 8500 Installation Manual

288 port switch
Table of Contents

Advertisement

Rev A04
The rack mounting holes conform to the IEA-310 standard for 19" racks.
Precautions should be taken to guarantee proper air ventilation in a fully populated and
cabled rack, and that the ambient temperature is maintained by allowing the air intake
from the front of the chassis to the exhaust side in the rack. Cabling must be taken into
account and not block air flow through the rack or through the chassis.
Table 10 - Rack Clearance Requirements
Area
Front of the rack
Rear side of the
rack
Sides of the rack
Space below the
chassis
Space on top of the
chassis
2.4

Power Requirements

Power requirements are useful for planning the power distribution system needed to support the
Vantage 8500 switch. Heat dissipation is an important consideration for sizing the air conditioning
requirements for an installation. Verify the available power source at the site for the type of device
you are installing.
To prevent a loss of input power, verify that the total maximum load on the cir-
cuit supplying power to the power supply is within the current ratings of the
wiring and breakers.
For added redundancy split the total maximum load across at least 2 circuits.

2.4.1 sPSU-S Units - Power Usage/Requirements

The Vantage 8500 switch requires multiple power connections using standard 3-wire (including a
safety grounding wire) AC power cords. The input voltage auto-adjusts for 100/240 VAC, 50Hz/
60Hz power connection.
34
Mellanox Technologies
Recommended Minimum Clearance
36" (90 cm) for technician access and maintenance
24" (60 cm) for human accessibility
No limits
There are two rack mount options. Option 1 is for an exact
U alignment whereby the rail kit occupies 3mm of the 1U
rack space under the chassis. Therefore, a minimum of 1U
clearance is required. However, your specific rack type may
require additional clearance.
Option 2 is for alignment with the hole above the 1 U mark-
ing. This does not require clearance under the chassis.
No limits
Installation Requirements