Indoor Unit, Outdoor Unit Mismatching Problem; Tank Type Problem - Daikin altherma 3 M Service Manual

Hide thumbs Also See for altherma 3 M:
Table of Contents

Advertisement

2.3.81 UA-00 – Indoor unit, outdoor unit mismatching problem
2.3.82 UA-17 – Tank type problem
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check that the AP mode is active (= WLAN adapter active as access point).
2 For more information about the configuration and further troubleshooting,
see the Daikin Residential Controller app or see the website:
www.onlinecontroller.daikineurope.com/
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Signal transmission
between outdoor and
indoor unit abnormality.
Improper combination of
outdoor and indoor unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check the wiring between the hydro PCB and the main PCB. See
circuit" [
4
 284].
Possible cause: Faulty wiring between the hydro PCB and main PCB.
2 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
3 Perform a check of the hydro PCB. See
Possible cause: Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
[E-05] is not set as 1, or
[E-07] is not set correctly.
Effect
Unit will stop operating.
"3.14 Main
"3.12 Hydro
Effect
Unit will stop operating.
2
Troubleshooting
|
http://
Reset
Power reset via outdoor
unit.
"4.1 Electrical
4
PCB" [
 171].
4
PCB" [
 160].
Reset
Power reset via outdoor
unit.
Service manual
65