Daikin altherma 3 M Service Manual page 185

Hide thumbs Also See for altherma 3 M:
Table of Contents

Advertisement

To check the fuse of the main PCB
To check the rectifier voltage of the main PCB
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Prerequisite: Turn OFF the respective circuit breaker.
1 Check that all wires are properly connected and that all connectors are fully
plugged‑in.
2 Check that no connectors or wires are damaged.
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 314].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier main PCB checks, see
4
procedures" [
 181].
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
a Fuse F7U
Blown fuse on the main PCB?
Yes
No
Prerequisite: First perform all earlier main PCB checks, see
4
procedures" [
 181].
1 Turn ON the power of the unit.
3
|
Action
No further actions required.
Return to
"Checking
procedures" [
4
 181] of the PCB and
continue with the next procedure.
a
Action
Replace the blown fuse, see
4
procedures" [
 190].
Return to
"Checking
4
procedures" [
 181] of the main PCB
and continue with the next procedure.
Components
"6.2  Wiring
"Checking
"Repair
"Checking
Service manual
185