Components
To perform an electrical check of the compressor
Service manual
136
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 134].
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10  V  DC before proceeding, see
electrical
hazards" [
2 Remove the cover of the compressor wire terminals.
a
a Compressor wire terminals cover
3 Disconnect the Faston connectors from the compressor wire terminals U, V
and W.
INFORMATION
Note the position of the Faston connectors on the compressor wire terminals to
allow correct connection during installation.
Action
Perform an electrical check of the
compressor, see
procedures" [
Replace the compressor and/or
damaged dampers, see
procedures" [
4
 285].
"3.7.1 Checking
4
 134].
"3.7.2 Repair
4
 140].
"3.7.1  Checking
"To prevent
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03