The flow through the 4-way valve is correct if the water temperature after the heat
exchanger rises/drops when operating in Heating/Cooling mode.
Is the flow correct?
Yes
No
INFORMATION
Follow this procedure when the outdoor temperature is outside the temperature
range for one of the operation modes (Heating or Cooling). The unit CANNOT
operate in the mode for which the outdoor temperature is outside its temperature
range. See the databook on Business Portal for the temperature range of the
operation modes.
1 With the unit operating, connect the service monitoring tool to the unit and
check whether the unit is operating in Heating or Cooling mode.
2 Check with a contact thermometer (or by touching) if the flow through the 4-
way valve corresponds with the flow shown in the flow diagram of the specific
operation mode. (See
INFORMATION
The flow through the 4-way valve is correct if the water temperature after the heat
exchanger rises/drops when operating in Heating/Cooling mode.
Is the flow correct?
Yes
No
3 Connect a manifold to one of the service ports of the refrigerant circuit and
check the pressure (suction, discharge). Compare with normal operation
conditions of the unit.
Refrigerant pressure correct?
Yes
No
When outdoor unit is combined with Heating only indoor unit
1 With the unit operating, connect the service monitoring tool to the unit and
check whether the unit is operating in Heating or Defrost mode.
2 Check with a contact thermometer (or by touching) if the flow through the 4-
way valve corresponds with the flow shown in the flow diagram of the specific
operation mode. (See
Action
4‑way valve is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
Replace the body of the 4‑way valve,
see
"3.2.2 Repair
4
"6.3 Piping
diagram" [
Action
4‑way valve is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
Perform the next step of this procedure.
Action
Replace the body of the 4‑way valve,
see
"3.2.2 Repair
Leaks may be found in the refrigerant
circuit. Perform a pressure test of the
refrigerant circuit, see
procedures" [
4
"6.3 Piping
diagram" [
4
procedures" [
 331]).
4
procedures" [
"4.2.1 Checking
4
 286].
 331]).
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
 101].
 101].