To perform a check of the backup heater contactor(s)
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Did the fuse blow or did the field
supplied circuit breaker of the backup
heater trip?
No
Prerequisite: First perform an electrical check of the backup heater, see
4
procedures" [
 104].
1 Measure the power supply voltage between the following terminals of the
backup heater contactor:
▪ K1M: 2‑4
The measured voltages MUST be 230 V AC ± 10%.
Is the measured power supply voltage
correct?
Yes
No
2 Check the power supply (source) of the backup heater.
Is the power supply (source) of the
backup heater correct?
Yes
No
3 With the Actuator test run still active, activate backup heater: step 1.
4 Measure the voltage between the following terminals of the backup heater
contactor.
▪ K1M: 1‑3 / 2‑4
The measured voltages MUST be 230 V AC ± 10%.
a Backup heater contactor K1M
3
Action
Return to
"Checking
4
procedures" [
 104] of the backup
heater and continue with the next
procedure.
Action
Skip the next step.
Continue with the next step.
Action
Correct the wiring and/or components
between the power supply (source) and
the backup heater contactor K1M, see
4
"6.2 Wiring
diagram" [
Adjust the power supply (source) of the
backup heater.
a
Components
|
"Checking
 314].
Service manual
107