2.3.74 U7-00 – Outdoor unit: Transmission malfunction between main microcomputer - inverter
microcomputer
2.3.75 U8-02 – Connection with room thermostat lost
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
2 Check if the remote controller user interface functions correctly. See
"3.21 User
interface" [
Possible cause: Faulty remote controller user interface.
3 Check the communication wiring between the remote controller and the unit.
See
"3.21 User
interface" [
Possible cause: Faulty wiring between the remote controller and the unit.
4 Check if the power supply is conform with the regulations. See
4
circuit" [
 284].
Possible cause:
▪ Faulty or disturbance of the power supply (imbalance >4%),
▪ Power drop,
▪ Short circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Communication
abnormality between
main and inverter
microcomputer.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the main PCB. See
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
Communication
abnormality between unit
and room thermostat
after connection was
already made.
4
 266].
4
 266].
Effect
Unit will stop operating.
"3.14 Main
Effect
Unit will NOT stop
operating.
2
Troubleshooting
|
"4.1 Electrical
Reset
Manual reset via user
interface.
4
PCB" [
 171].
Reset
Automatic reset.
Service manual
61