To install the water pump wiring harness
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
3 Cut all tie straps that fix the wiring harness, and remove the wiring harness
from the unit.
4 To install the water pump appropriate wiring harness, see
4
procedures" [
279].
1 Connect the wiring harness to the appropriate connector:
▪ X16A on hydro PCB for power supply wiring harness
▪ X25A on hydro PCB for PWM signal wiring harness
2 Route the wiring harness towards the water pump and connect the wiring
harness to the appropriate connector (power supply and/or PWM signal) of
the water pump.
3 Fix the wiring harness using new tie straps.
Is the problem solved?
Yes
No
3
|
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Components
"3.24.2 Repair
Service manual