Advertisement

16.5

Overhead Presence Detection and Interlock (Level 4)

a Disconnect batteries if any.
b Disconnect the mains.
c Press the LEARN BUTTON (LRN) and keep it depressed.
d Connect the mains.
e Watch the ERROR LED.
3 s
f
Release the LEARN BUTTON after 4 flashes (LED is out).
g Identify the current monitoring
The ERROR LED flashes an amount of short flashes that correspond to the status number.
After a short pause the LED will repeat the status number and so on.
h Changing the status
If you push the LEARN BUTTON once, the status number will increase. When you have reached
the highest status number it will start at number one again.
Level 4:
OPD-monitoring
Interlock*
* Interlock cannot be used together with OPD-sensors. If (Locked) is used the operator must
be in EXIT or OFF mode.
• Disconnect the mains
Next time you connect the mains the operator will use the new status setting.
i
Interlocking connections. Can be used as security interlock.
Operator 1
1020527-DIen-3.0
1 s
3 s
1 s
1 (Default)
2
OFF
ON
OFF
OFF
Operator 3
Operator 2
Interlock ON
Interlock OFF
Issue 2021-06-07
3 s
3 s
1 s
3
4
OFF
OFF
Operator 2
Operator 2
to 6
to 6
(Locked)
(Closed)
Operator 5
Operator 4
16 Advanced settings
5
6
OFF
OFF
Operator 1
Operator 1
(Locked)
(Closed)
Operator 6
81