12 Electrical connection
12.3

Double door installations

There are three different types of double door installations:
• Rebated Has an overlapping primary door, can be opened synchronously if it is not jamming
and must be closed asynchronously to avoid that the doors will jam or close in the wrong order.
• Jamming This door type needs to be opened and closed asynchronously to avoid that the
doors will jam with each other.
• Not jamming, not rebated This door type has doors that always can move independently of
each other and can be opened and closed synchronously.
12.4

Settings for double doors

Function
Common
Program selection
Opening time
Closing time
Hold open time
Close / Continue to open when the door is obstructed
PAG On/Off
SOS On/Off
Level of Power assist
Extended closing torque
OPD/OPS Impulse or Mat Logic Impulse
Selection of operating mode during operation on battery
power
Individual
Lock/Unlock signal voltage
Locked without/with power
Lock release Enable/Disable
Open Delay Time
Lock kick Enable/Disable
* For "Double egress doors", these functions must be set separately for primary and secondary as
the arm systems as well as the air pressure may be different.
Note!
• Locks on the primary and secondary doors must be connected to the control unit (CU) on the
corresponding operator.
• Inner and outer impulses can be connected to either primary or secondary CU or both.
• The OPD/OPS is to be connected to the primary CU except for "Double egress", where each
OPD/OPS must be connected to corresponding CU.
• Door leaf mounted sensors must always be connected to corresponding CU.
64
Issue 2021-06-07
Settings on the
Primary
Secondary
X
X
X
X
X
X
X
X
(X)*
X
(X)*
X
X
X
X
X
X
X
X
X
X
X
X