12.1.4

Extension unit DAB905ESE

This extension unit has inputs for electro-mechanical lock, program selector, batteries, KILL function, OPEN/CLOSE,
KEY opening and outer impulse.
Functions
Battery backup unit
0.5 s
0 s
3 s
ON
1
2
3
4
5
DIP-switches
shown in OFF
position
1 Lock 12 V (OFF) / 24 V (ON)*
Lock 12 V ( OFF ) / 24 V ( ON)*
2 Locked without power (OFF) / with power (ON)*
Locked without power (OFF ) / with power (ON)*
2)
Lock release*
3 Lock release2)
1)
4 Lock kick1)
Lock kick
Battery monitoring
5 Battery monitoring
1)
Position OFF: Smooth closing, to be used on doors without lock.
Position ON: More powerful closing, to be used on doors with lock, to overcome binding in the locking device (inactivated
for Inverse door).
2)
If the switch is set to ON, the LOCK RELEASE is active during the opening delay time set by the potentiometer.
For PAIR OF DOORS installations, the LOCK RELEASE works in sequence: First the primary door then the secondary door.
Note! Lock only functions when Program Selector is in OFF or EXIT.
*
After changing any system selection a new LEARN must be carried out.
With selection 'Locked without power' is the lock energized from 0 to 10 degrees at opening.
If a program selector is not used, a jumper is required from position 3 to position 11.
1020527-DIen-3.0
+24 V DC
(+) 24 VDC
OPEN
Program selector
EXIT
OFF
Unlocked signal from lock
UNL
KRST
KILL reset (see jumper below)
KILL impulse
KILL
Key impulse (1.5-30 s)
KEY
OPEN / CLOSE impulse (latching relay)
O/C
OIMP
Outer impulse
(-) 0 VDC Ground
GND
Electro-mechanical locking device (12V DC max. 1200 mA / 24 V DC
max 600 mA, see DIP-switch No. 1 below)
+
Potentiometer for opening delay
Automatic kill reset (jumper on)
Manual kill reset (jumper off)
Issue 2021-06-07
2)
12 Electrical connection