Siemens Climatix S300 HRV Application Manual page 46

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Configuration
4
Configuring the hardware
4.5.2.2 Extension module
Output Q21
Output A21
46 | 170
The following functions can be selected for output signals on the extension module
POS9:
Parameter
Selection for Q21
Selection
None
Outside air damper command
Fire damper command
Preheating coil electric command
Preheating coil pump command
Earth-to-air heat exchanger bypass
damper command
Heat exchanger bypass damper command HExgDmpBypCmd
Electric heating coil command
Heating coil pump command
Cooling coil pump command
Cooling coil DX evaporator command
Dehumidifier free-standing command
A-Alarm indication output
B-Alarm indication output
Common alarm indication output
Operation indication output
Parameter
Selection for A21
Selection
None
Supply air fan speed
Exhaust air fan speed
Preheating coil electric position
Heat exchanger bypass damper position
Rotary heat exchanger speed
Heating coil electric position
Heating coil valve position
Cooling coil valve position
Cooling coil DX evaporator position
BACnet object
Q21Sel, STR_VIEW,71
BACnet object
R/W
Signal type
-
-
-
DmpOaCmd
R/W
Relay
FdpCmd
R/W
Relay
PreHclElCmd
R/W
Relay
PreHclPuCmd
R/W
Relay
EaHxDmpbCmd
R/W
Relay
R/W
Relay
HclElCmd
R/W
Relay
HclPuCmd
R/W
Relay
CclPuCmd
R/W
Relay
CclDxCmd
R/W
Relay
DhumFrsdCmd
R/W
Relay
AalmIndOut
R/W
Relay
BalmIndOut
R/W
Relay
CmnAlmIndOut
R/W
Relay
OpIndOut
R/W
Relay
BACnet object
A21Sel, STR_VIEW,272
BACnet object
R/W
Signal type
-
-
-
FanSuSpd
R/W
0...10V
FanEhSpd
R/W
0...10V
PreHclElPos
R/W
0...10V
HExgDmpBypPos
R/W
0...10V
RotHExgSpd
R/W
0...10V
HclElPos
R/W
0...10V
HclVlvPos
R/W
0...10V
CclVlvPos
R/W
0...10V
CclDxPos
R/W
0...10V
Range
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Range
0...100 %
0...100 %
0...100 %
0...100 %
0...100 %
0...100 %
0...100 %
0...100 %
0...100 %
A6V10733786_en_c