Available parameters
A6V10733786_en_c
Shut-down for Maintenance
The air conditioner can be switched off, e.g. for maintenance work, using BI or the
BACnet object. In this case, the shutdown sequence is started and the system
performs a controlled shutdown. The stop sequence is executed by activating the
input PrtOpModRIn or the BACnet object PltShD. These functions override all other
influences except the emergency control, protection control and operation via BI.
Current values
Plant start / stop state
Initiate controlled shutdown
BI controlled shutdown
Basic settings
Delay time after power-on, startup step 2 DlyPwrUpHrv
Timeout for water heating coil purge,
startup step 4
Runtime for outside air dampers, startup
step 5
Delay time for exhaust fan only, startup
step 6
Delay time supply fan ramp up, startup
step 7
Delay time before normal operation,
startup step 8
Delay time cooldown electric heaters,
shutdown step 2
Application functionalities
Start-up / shut-down sequence
BACnet object
R/RW
Note
PltSttStpSta
R
1: off
MVAL,397
2: Purge heating coil
3: Open dampers
4: Startup exhaust fan
5: Startup supply fan
6: Prepare normal operation
7: Normal operation
8: Cooldown el. Heater
9: Ramp down fans
10: Close dampers
11: Ramp down ERC
12: Power up delay
PltShdn
RW
0:Inactive
BVAL,266
1: Active
PrtOpModRIn
R
0: Inactive
BI,85 (D1)
1: Active
BI,102 (D2)
BI,119 (X3)
BI,136 (X8)
BACnet object
R/RW
Note
RW
s [min value 120 sec, if fire
dampers are used]
PINTVAL,130
DlyMaxFrpSttUp
RW
sec.
PINTVAL,109
DlyOnAflVntReq
RW
sec.
PINTVAL,81
DlyOnAflEhSta
RW
sec.
PINTVAL,129
TiSttUpSpdVnt
RW
sec.
PINTVAl,104
DlyOnAirFlSta
RW
sec.
PINTVAL,103
DlyOffAflHldH
RW
sec.
PINTVAL,107
5