Orientation
Commissioning
When commissioning, check both wiring and functioning of the actuator.
Actuator stem extends
Actuator stem retracts
The actuator must be commissioned only with a correctly mounted valve in place!

Self-calibration

When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully
extended ➙ setpoint).
Fully retracted
Fully extended
Never intervene manually during self-calibration.
Correct calibration is only possible with valve stroke > 0.05 inch (1.2 mm). Valve stroke
< 1.2 mm results in calibration failure.
If calibration fails, the actuator performs another calibration automatically after
10 seconds.
After three failed calibration attempts, the actuator stem remains in the extended
position and the valves are open.
Manual operation
A 3-mm hexagonal wrench can be used to move the actuator to any position.
Siemens
Smart Infrastructure
NOTICE
Calibration
Y
Power
On
CAUTION
NOTICE
Normally open valve closes, normally closed
valve opens
Normally open valve opens, normally closed
valve closes
t
5
A6V12681514_enUS_b
06/15/2023