Available parameters
A6V10733786_en_c
Current values
Supply air temperature
Outside air temperature
Present temperature setpoint
Present setpoint shift heating
Present setpoint shift cooling
Standard parameters
Setpoint supply air temperature comfort
Setpoint difference cooling for comfort
Setpoint difference heating comfort
Setpoint supply air temperature economy
Setpoint difference cooling economy
Setpoint difference heating economy
Setpoint supply air temperature unoccupied
Setpoint difference cooling for unoccupied
Setpoint difference for heating unoccupied
Special settings
TOa limitation for heating release
TOa limitation for cooling release
Setpoint heating protection
Setpoint cooling protection
Testing and debugging
Heating / cooling state
Delay heating cooling changeover
Application functionalities
Air temperature control
BACnet object
R/RW
TSu
R
AI,52
TOa
R
AI,51
SpT
RW
AVAL,598
PrSpShftH
R
AVAL,96
PrSpShftC
R
AVAL,128
BACnet object
R/RW
SpTCmf
RW
AVAL,97
DSpCCmf
RW
AVAL,392
DSpHCmf
RW
AVAL,390
SpTEco
RW
AVAL,296
DSpCEco
RW
AVAL,306
DSpHEco
RW
AVAL,299
SpTUcd
RW
AVAL,297
DSpCUcd
RW
AVAL,307
DSpHUcd
RW
AVAL,300
BACnet object
R/RW
HLmCmf
RW
AVAL,105
CLmCmf
RW
AVAL,132
SpHPrt
RW
AVAL,100
SpCPrt
RW
AVAL,129
BACnet object
R/RW
HCSta
R
MVAL,128
DlyOnHCChovr
RW
PINTVAL, 68
5
Unit / Note
°C
°C
°C
includes weather
compensation
K
shows winter
compensation
K
shows summer
compensation
Unit
°C
K
K
°C
K
K
°C
K
K
Unit
°C
°C
°C
°C
State
1: Neither
2: Heating
3: Cooling
85 | 170