Siemens Climatix S300 HRV Application Manual page 112

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Application functionalities
5
Heating
Frost protection function
while unit is in operation
Frost protection while the
unit is not in operation
Available parameters
112 | 170
The application uses a two-stage antifreeze with 2 special setpoints, which is
intended to prevent freezing while the ventilation is still normally active, and to
protect the device when prevention has not been sufficient. The temperature
sensor TFrPrtHcl is required for this function and must be located at the coldest
point of the water heating coil.
Stage 1 - Frost risk:
If the temperature of TFrPrtHcl falls below the set frost risk setpoint (e.g. 10°C), the
pump is switched on (if not already switched on) and the valve is controlled
according to the temperature of TFrPrtHcl at risk of frost. When the temperature of
TFrPrtHcl reaches the frost hazard set point, the frost protection function is
automatically terminated.
Stage 2 – Frost protection:
If the temperature at TFrPrtHcl falls below the set frost protection setpoint (e.g.
4°C), the pump is switched on (if not already switched on), the valve is opened
100%, the ventilation is switched off, any fresh air dampers are closed and the A
alarm is activated.
A restart can only take place, after the alarm is acknowledged, the temperature is
higher than SpFrPltOnHcl and the plant is reset.
During the times when the ventilation unit is switched off for any reason (must still
be connected to power supply), the temperature of TFrPrtHcl has an additional
setpoint (e.g. +25°C) to secure the start-up situation. If the heating coil is constantly
kept warm, it will not drop to the frost protection limit during start-up, even in cold
outdoor conditions.
The pump runs constantly during the non-productive times of the ventilation unit. If
the temperature of TFrPrtHcl falls below the set temperature limit during the device
failure times, the valve is PI-controlled to reach the idle setpoint. The alarm is not
activated until the temperature at the TFrPrtHcl drops below the frost protection set
point.
If one of the frost protection parts is active, the standard temperature control has
no priority (constant or cascaded).
The function is activated automatically when HclHw11y is commissioned.
Current value
Return temperature setpoint for frost
Return temperature value
Basic settings:
Frost protection limit
Setp.frost prot.if plant on, heat.coil
Setp.frost prot.if plant off, heat.coil
Max.delay frost protection for startup
When passed, startup is stopped and frost
alarm is raised
BACnet object
SpFrPrt
AVAL,216
TFrPrtHcl
AI,58 (B3)
AI,64 (B4)
AI,80 (X8)
AVAL,317 (POS9)
AVAL,468 (QBM)
BACnet object
R/RW
FrPrtLm
RW
AVAL,217
SpFrPltOnHcl
RW
AVAL,218
SpFrPltOffHcl
RW
AVAL,219
DlyMaxFrpSttUp
RW
PINTVAL,109
R/RW
Note
R
°C
R
°C
Note
°C, plant shutdown,
valve open, pump on
°C
°C
sec.
A6V10733786_en_c