ERC efficiency calculation
TOa
Outside air [°C]
TEx
Extract air temperature [°C]
TSuAfHexg
Supply temperature after heat
exchanger [°C]
Efficiency n is calculated on the exhaust side by the following formula:
n = (TEx – TEh) / (TEx – TOa)
In case the preheating coil is active, TSuAfPreHcl is used instead of TOa. If the
sensor is not available while the preheating coil is active, the efficiency is
unreliable.
If an additional supply air sensor after the heat exchanger is available, the
efficiency n is calculated on supply and exhaust side as:
n = 0.5 * (TEx – TEh) / (TEx – TOa) + 0.5 * (TSuAfHexg – TOa) / (TEx – TOa)
Efficiency calculation requires at least outside temperature, extract temperature
and exhaust temperature sensors.
Current values
ERC efficiency
TEh
Exhaust air temperature [°C]
TSuAfPreHcl
Supply temperature after
preheating coil [°C]
BACnet object
R/RW
PrHExgEfcy
R
AVAL,161