Siemens Climatix S300 HRV Application Manual page 95

Heat recovery ventilation with controllers
Table of Contents

Advertisement

A6V10733786_en_c
Basic settings
De-icing mode configuration
De-icing, stage1 limit, heat exchanger
De-icing, stage2 limit, fan
Activation time de-icing
De-icing rotor speed
De-icing supply fan flow
De-icing exhaust fan flow
De-icing supply fan pressure
De-icing exhaust fan pressure
De-icing supply fan speed
De-icing exhaust fan speed
Special settings
Temperature drop for room extract
humidity of 20% r.h.
Temperature for maximum off time
Maximum off time
Temperature for minimum off time
Minimum off time
Application functionalities
Energy Recovery
BACnet object
R/RW
DeicModCnf
RW
MVAL,408
SpTDeicHExg
RW
AVAL,177
SpTDeicFan
RW
AVAL,173
TiDeic
RW
PINTVAL,90
HExgSpdDeic
RW
AVAL,178
SpAirFlSuDeic
RW
AVAL,181
SpAirFlEhDeic
RW
AVAL,226
SpPSuDeic
RW
AVAL,196
SpPExDeic
RW
AVAL,232
SpFanSuSpdDeic
RW
AVAL,208
SpFanEhSpdDeic
RW
AVAL,238
BACnet object
R/RW
DiffTHuCmpDeic
RW
AVAL,176
TDeicTiOffStt
RW
AVAL,179
TiOffDeicMax
RW
PINTVAL,91
TDeicTiOffEnd
RW
AVAL,180
TiOffDeicMin
RW
PINTVAL,92
5
Note
1: None
2: Erc fix
3: Erc fix + Fans
4: Erc fix + Preh
5: Erc fix + Fans + Preh
6: Erc TEh
7: Erc TEh + Fans
8: Erc TEh + Preh
9: Erc TEh + Fans + Preh
°C
°C
sec.
%
m3/h
m3/h
Pa
Pa
%
%
Note
K
°C
sec.
°C
sec.
95 | 170