Siemens Climatix S300 HRV Application Manual page 139

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Code
Alarm
Name/Description
Class
1033
B
Extract air pressure,
sensor fault
1034
B
Differential pressure supply
air fan, sensor fault
1035
B
Differential pressure exhaust
air fan, sensor fault
1037
A/B/n
Supply air fan fault
1038
Exhaust air fan fault
Code range for - Application
2001
A
Emergency off
2002
A
Smoke detector
2004
A
Fire alarm
2005
B
Supply air temperature,
exceeds operating limits
2007
A
Heating coil, frost warning
2010
A
Heating coil, over
temperature
2012
A
Preheating coil,
overtemperature
2013
A
Outside air damper stops air
flow
2017
A/B/n
Heat exchanger efficiency
supervision
Code range for - Communication
3005
B
I/O extension modul, Modbus
communication fault
3011
B
Duct pressure sensor,
Modbus communication error
3012
A/B
Supply air fan, Modbus
communication fault
3013
A/B
Supply air fan, Modbus
communication fault
3101
B
Room sensor, KNX PL-Link
communication error
A6V10733786_en_c
Source
Plant
BACnet object / Comment
lock
System Run
PEx,
active only if VntCtl12 selected
System Run
DiffPFanSu,
active only if sensor available
System Run
DiffPFanEh,
active only if sensor available
Proces
conf.
FanSuSpdFb, FanSuFlt
s
Check of fan speed feedback or
fault signal
Proces
conf.
FanSuSpdFb, FanSuFlt
s
Check of fan speed feedback or
fault signal
Proces
Stop
EmgOff (BI)
s
Proces
Stop
Smext (BI)
s
Proces
Stop
Supply (TSu) or extract (TEx) air
s
temperature exceeds max. limit
Proces
Run
Supply air temperature (TSu)
s
exceeds min/max limits
Proces
Stop
Temperature (TFrPrtHcl) below
s
frost protection limit ,
active only if HclHw selected
Proces
Stop
HclOvrTDet (BI),
s
active only if HclEl selected
Proces
Stop
PreHclOvrTDet,
s
active only if PreHclEl selected
Proces
Stop
s
Proces
Conf.
Plausibility check of air
s
temperatures
System Run
POS9,
active only if device configured
System Run
QBM,
active only if device configured
System Conf.
Active only if Modbus fan
configured
System Conf.
Active only if Modbus fan
configured
System Run
Common fault for all PL-Link
room devices:
POS8.4420/4440,
QMX3.P30/P40/P70,
active only if device configured
Application functionalities
Alarm functions
Influence of alarm
Fallback to supply air control, linear
fan speed if all sensors fail
Fallback to linear fan speed, if in air
flow control
Fallback to linear fan speed, if in air
flow control
Shutdown AHU / No reaction / No
reaction
Shutdown AHU / No reaction / No
reaction
AHU off
Smoke extract mode
Shutdown AHU
No reaction
Shutdown AHU, Frost protection
mode: Switch on pump, open valve
Shutdown AHU
Shutdown AHU
Shutdown AHU
Shutdown AHU /
Bypass or shutdown / no reaction
Same reaction as for each
connected input
Fallback to linear Fan speed
A: Shutdown AHU /
B: No reaction
Reaction of fan based on fan
device configuration
A: Shutdown AHU /
B: No reaction
Reaction of fan based on fan
device configuration
139 | 170