Choosing The Functions - Siemens Climatix S300 HRV Application Manual

Heat recovery ventilation with controllers
Table of Contents

Advertisement

4.3 Choosing the functions

Control functions
Control function
BACnet object
Ventilation control
STR_VIEW, 402
Temperature
STR_VIEW, 103
control
Kitchen hood
STR_VIEW, 168
ventilation
operation
Fireplace
STR_VIEW, 112
ventilation
operation
Dehumidification
STR_VIEW, 115
control
Particulate matter
STR_VIEW, 324
control
Air quality control
STR_VIEW, 352
A6V10733786_en_c
Refer to the list below to set the functions of the application accordingly. Some of
the functions may require certain hardware (peripheral devices).
Selection
Ventilation control 21y, air
volume flow
Ventilation control 22y, air duct
pressure
Ventilation control 23y, fan
speed
Supply air temperature control
21y
Temperature cascade control
21y
None
Active
None
Active
None
Active
None
Active
None
Active
Choosing the functions
Note
Controls the measured air flow to values depending on
the operating mode and air quality
Controls supply and extract air duct pressure to values
depending on the operating mode and air quality
Controls supply and extract fan speed to values
depending on the operating mode and air quality (default)
Controls supply air temperature to a value depending on
the outside air temperature modulating the available
actuators (default)
Controls room or extract air temperature to a value
depending on the outside air temperature modulating the
supply air temperature setpoint
No kitchen extract fan available (default)
Kitchen extract fan available (default)
No open fireplace available
Open fireplace available (default)
No humidity control available (default)
Dehumidification control via fan speed and / or stand-
alone dehumidifier
No particulate matter control available (default)
Particulate matter control available
No air quality control available (default)
Air quality control available
Configuration
4
29 | 170