Ebm-Papst Exhaust Air Fan - Siemens Climatix S300 HRV Application Manual

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Engineering of communicative devices
6
Modbus components

6.2.5 Ebm-papst exhaust air fan

Notes
I/O reliability & control
Exhaust fan error code
Exhaust fan warning code
Exhaust fan reset
152 | 170
Slave address: 2
The fan configuration must be set with ebm-papst tool "EC Control"
The configuration depends on the specific use case
The following settings are required or recommended
Setting
Communication parameters
Device status
Fail-safe function
For additional information please refer to the manufacturer's web site
www.ebmpapst.com.
You can contact a local representative, access downloads and get more technical
information for the fan.
BACnet object / device register assignment
Actual I/O
BA-objects
values
Exhaust air fan
FanEhSpd
speed
AO,150
Exhaust air fan
FanEhFlt
fault
BI,145
Exhaust air fan
FanEhSpdFb
speed
AI,164
feedback
Exhaust air fan
FanEhTotOph
total operating
AI,162
hours
BA-object
R/W
FanEhErrCode
R
AVAL,688
FanEhWrnCode
R
AVAL,689
FanEhRst
RW
BO,103
Parameter
Device address (required)
Communication speed (required)
Communication parity (required)
Source of set value (required)
Save set value to EEPROM (required)
Fail-safe mode (recommended)
Set fail safe speed % (recommended)
R/W
Note
RW
R
R
R
Note
0: No error
> 0: see ebm-papst
0: No error
> 0: see ebm-papst
Pulse, executed by
acknowledge or reset
Value
1
19200
8E
RS485/Bus
No
Fail safe speed value
0
https://
Register
Function code
Address
53250
06: Write single
53266
04: Read input
Bit 4
53265
04: Read input
53258
03: Read
holding
Register
Function code
address
Polling /
heartbeat / COV
53266
04: Read input
53267
4: Read inpu
53249
06: Write single
Bit 0
A6V10733786_en_c