Heat recovery ventilation with controllers
Table of Contents

Advertisement

Application functionalities
5
Fire damper (Fdp11y)
Available parameters
128 | 170
FireDmp1
S2
S6
Current values
Fire damper status
Fire damper feedback
Fire damper open
Prio2: Fire / Smoke
Prio5: Protection from plant control
Fire damper alarm
Fire damper test active
Basic settings
Activate fire damper test
Damper opening time
Damper closing time
Testing and debugging
Fire damper closed by control
program
FireDmp2
S2
S1
S4
S6
BACnet object
R/RW
FdpSta
R
MVAL,160
FdpFb
R
DI,73 (D1)
BI,90 (D2)
BI,107 (X3)
BI,124 (X8)
FdpCmd
RW
BO,51 (Q1)
BO,66 (Q2)
BO,81 (Q3)
BVAL,242 (POS9)
FdpAlm
R
BVAL,165
FdpTst
R
BVAL,212
BACnet object
R/RW
MntnSched
SCHED,3
TiOpnFdp
RW
PINTVAL,117
TiClsFdp
RW
PINTVAL,118
BACnet object
R/RW
FireAlm
R
BVAL,163
S1
BI
S4
Note
1 = moving
2 = closed
3 = open
4 = no move
5 = no close
6 = no open
0 : one or more dampers not
opened or closed
1: all fire dampers in open or
closed end position
Fire damper closes
unexpectedly or test failed
Fire damper test actually
running
Note
Activation via weekly
maintenance with BACnet
scheduler
sec.
sec.
Note
A6V10733786_en_c