Modbus Components - Siemens Climatix S300 HRV Application Manual

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Engineering of communicative devices
6

Modbus components

6.2 Modbus components
General rule
Protocol parameters
Available parameters
146 | 170
Devices that can be connected to Modbus master Interface
Device
Description
POS9.1515
IO extension
QBM97 (1)
Air pressure sensor # 1
QBM97 (2)
Air pressure sensor # 2
FanSu
EBM Papst supply air fan
FanEh
EBM Papst exhaust air fan
Baud rate 19200
Parity
Even
Stop bits
1
Communication monitoring
Communication with the slave devices is constantly monitored. The monitoring is
activated as soon as the device is selected (basic configuration).
If the communication with the device cannot be established or gets lost, individual
alarm is triggered:
B-Alarm "3005: I/O extension module, Modbus communication error"
B-Alarm "3011: Duct pressure sensor, Modbus communication error"
Configurable "3012: Supply air fan, Modbus communication error"
Configurable "3013: Exhaust air fan, Modbus communication error"
An adjustable delay time to avoid false alarms due to short disturbances can be
configured.
Actual values
BA-object
Delay for
DlyComErr, PINTVAL, 80 RW
communication error
Address
Note
41
40
DIP switch setting required
42
DIP switch setting required
1
Configuration with EBM Papst tool required.
Must be used together with EBM Papst
exhaust air fan
2
Configuration with EBM Papst tool required.
Must be used together with EBM Papst supply
air fan
R/RW
Note
The alarm is triggered as soon the set
time has elapsed.
Default = 120s
A6V10733786_en_c