Orientation
Installation
●
Observe all admissible temperatures (see "Technical data
●
Do not twist the cable.
●
Magnets can damage the actuator.
●
Provide a means for isolation from the power supply, e.g., connecting a circuit breaker or
switch fuse upstream of the control unit.
National safety regulations
Failure to comply with national safety regulations may result in personal injury and property
damage.
●
Observe national provisions and comply with the appropriate safety regulations.
Phase cut and pulse-duration-modulated (PDM) signals are not suitable.
Regulations and requirements to ensure the safety of people and property must be
observed at all times!
Commissioning
When commissioning, check both wiring and functioning of the actuator.
●
Actuator stem extends Normally open valve closes, normally closed valve opens
●
Actuator stem retracts Normally open valve opens, normally closed valve closes
The actuator must be commissioned only with a correctly mounted valve in place!
Self-calibration
When operating voltage is applied, the actuator self-calibrates (fully retracted ➙ fully
extended ➙ setpoint).
Siemens
Smart Infrastructure
A [mm]
B [mm]
5.5
6.0
Crimp ferrule on stripped wire of connecting cable.
CAUTION
CAUTION
NOTICE
C [mm]
35
[▶
10]").