Input Settings - Siemens Climatix S300 HRV Application Manual

Heat recovery ventilation with controllers
Table of Contents

Advertisement

4.5.1 Input settings

4.5.1.1 Controller board
Input B1, B2, B3, B4
Input X1
A6V10733786_en_c
The following functions can be selected for input signals on the controller board:
Parameter
Selection for B1
Selection for B2
Selection for B3
Selection for B4
Selection
None
Supply air temperature
Outside air temperature
Extract air temperature
Exhaust air temperature
Supply air temperature after heat
exchanger
Supply air temperature after
preheating coil
Flow temperature preheating coil
Frost protection temperature for
heating coil
Parameter
Selection for X1
Selection
None
Supply air fan speed feedback
pulse
Supply air fan speed feedback
voltage
Extract air quality
Relative humidity for extract air
Particulate matter in room
Configuring the hardware
BACnet object
B1Sel,
STR_VIEW,41
B2Sel,
STR_VIEW,43
B3Sel,
STR_VIEW,45
B4Sel,
STR_VIEW,47
BACnet object
R/W
Signal type
TSu
R
NTC10k
Toa
R
NTC10k
TEx
R
NTC10k
TEh
R
NTC10
TSuAfHExg
R
NTC10k
TSuAfPreHcl
R
NTC10k
TFlPreHcl
R
NTC10k
TFrPrtHcl
R
NTC10k
BACnet object
X1Sel,
STR_VIEW,53
BACnet object
R/W
Signal type
-
-
-
FanSuSpdFb
R
0...300Hz
FanSuSpdFb
R
0...10V
AQualEx
R
0...10V
HuRelEx
R
0...10V
PmR
R
0...10V
Configuration
4
Range
-50...80 °C
-50...50 °C
-50...80 °C
-50...80 °C
-50...80 °C
-50...80 °C
-50...80 °C
-50...80 °C
Range
0...100 %
0...100 %
0...2000 ppm
0...100 %
0...500 µg/m3
37 | 170

Hide quick links: