Siemens Climatix S300 HRV Application Manual page 151

Heat recovery ventilation with controllers
Table of Contents

Advertisement

Remark
A6V10733786_en_c
The above information is available for all ebm-papst Modbus fans with interface
version >= 5.0 (2012). Depending on the type of fan, additional information is
available. The application does not read this additional information, as reading
causes malfunction on some types of fans.
Error and warning codes are shown as decimal value, for example error code '17'.
They must be converted into a bit string, for example '0000 0000 0001 0001'.
According to EBM Papst documentation, this means FB (General fan fault) and
PHA (Phase error).
When using a Modbus fan, both fans must be Modbus fans.
Engineering of communicative devices
Modbus components
6
151 | 170

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents